Dry Fire Hydrant Repair & Maintenance #13 - Defective Head Replacement
Email Print RSS Facebook Twitter RSS

By President Mark Davis
November 11, 2021

We recently completed a dry fire hydrant suction head replacement project in Carroll County, MD. The local FD reported a seized suction head cap. We investigated the 4-1/2" brass fitting and found that it was in fact seized. Applying heat, penetrating solvents, and good old big-boy muscle power did nothing to budge the cap. So.... we cut off the head and replaced it with a new, 6-inch NST male suction head which brought the system up to the current County standard.

Before installing the new head, we first installed a temporary head and took draft to make sure that the rest of the system worked....and it did. The new head was installed, the system was painted using UV- resistant spray paint, and a flow test was completed....1,000+ gpm.

Website Designed and Hosted By: Content Proudly Maintained By: Contact Info:
Firehouse Solutions
www.FirehouseSolutions.com
GBW Associates, LLC
3178 Cardinal Drive
Westminster, MD 21157

Emergency Dial 911
Phone: 443-398-6619
E-mail: thebigcamel@gotbigwater.com
Copyright © 2024 Firehouse Solutions (A Service of Technology Reflections, Inc.)