By President Mark Davis
March 27, 2014

A barrel-type suction strainer performs best when there is sufficient water below it and above it - that is why the barrel strainer is the type of suction strainer most often chosen for use when conducting the pump certification test at a "test pit." The barrel strainer is also the type most likely to provide maximum flow in regards to achieving pump capacity.

In terms of achieving high-flows and rated pump capacities, barrel strainers do work in dump tanks - however, the big issue is the vortex created once the water level begins to drop in the tank. The size of the vortex and the point at which it occurs depends some on the rate at which water is being taken out of the tank. The higher the flow rate, the faster the vortex will occur. This leads to limiting the volume of water available for use in the dump tank.

For example, using a 6-inch barrel strainer - placed flat on the bottom of the dump tank - automatically eliminates the bottom 6-inches of water from avalable flow. Add in the vortex, and you might find that you only have half the capacity of the dump tank available because the vortex often starts about 8 to 10 inches above the strainer.

The bottom line is that while not ideal in terms of using t total dump tank capacity, when faced with no other strainer choice - the pump operator needs to understand the limitations of the barrel strainer when used in a dump tank operation.

 
Website Designed and Hosted By: Content Proudly Maintained By: Contact Info:
Firehouse Solutions
www.FirehouseSolutions.com
GBW Associates, LLC
3178 Cardinal Drive
Westminster, MD 21157

Emergency Dial 911
Phone: 443-398-6619
E-mail: thebigcamel@gotbigwater.com
Copyright © 2026 Firehouse Solutions (A Service of Technology Reflections, Inc.)