Two, 500 gpm pumps are used to keep this dump tank full so that the pumper can fill tankers at 1,000 gpm.
|
|
This open relay is an efficient way to use portable pumps that otherwise would not provide enough intake pressure at the suction inlet on the pumper.
|
|
| |
The use of 5-inch LDH made a huge difference in this operation because it allowed water to be moved over 300-feet with little friction loss - thus maximizing the pump's output for the hose set-up.
|
|
Another factor that "worked in the favor" of the operation was lift. The lift was less than 3-feet, therefore the portable pumps could commit their workload to discharge operations.
|
|
| |
One limiting factor when using portable pumps is fuel consumption. However, at this 2-hour drill, fuel consumption was not an issue.
|
|
The 300-ft lay of 5-inch hose was impressive.
|
|
| |
This 1,000 gpm pumper was able to draft from the dump tank and fill tankers at 1,000 gpm using LDH. This most likely could not have happened had the portable pumps fed the pumper directly - the pumper's intake pressure would have been too low thus causing the LDH to collapse and cavitation to occur.
|
|
| |